JDB-11 Marine AC Network Insulation Monitoring And Alarm

Item No.: 02537
Advanced converter line and Indicating device integration structure,the instrument is high accuracy and large angle.Null meter reading instrument all have zero button,easy to adjust.
Description
Description

JDB-11 Marine AC Network Insulation Monitoring And Alarm

Model number:Q96-ZMΩ F96-MΩ AH96-MΩ 51L5-MΩ(without alarm signal output insulation meter,Wide angle 240 degree)
Model number:Q96-MΩ F96-MΩ AH96-MΩ (without alarm signal output insulation meter,Right angle 90 degree)

Model number:Q96-ZMΩA F96-BMΩ AH96-BMΩ51L5-BMΩ (with alarm signal output insulation meter,Wide angle 240 degree)

Model number:F96-BMΩ Q96-MΩA AH96-BMΩ (with alarm signal output insulation meter,Right angle 90degree)

Model number:F96D-BMΩ Q96D-MΩA AH96D-BMΩ (Double circuit alternating Current Network Insulation Electrical Resistance Monitor,double structure)

Q/F 96-BMΩ Alternating Current Network Insulation Electrical Resistance Monitor can be used to monitoring the non ground connection type alternating power distribution system which is below 500V continuously,and it will produce soundlight alarm signal when the electrical circuit insulation electrical resistor when exception occurs,insulation electrical resistance lower than the alarm value of instrument.

The effective meter measure range is 0.005-5Ω,alarm value class have 0.005KΩ, 0.1KΩ,0.2KΩ,0.5KΩ,1KΩ,total five class. or alarm value

Application Of Our Marine Meter:

Its structure is magnetic electric tension string supporting and pivot needle type structure.

Rotating part no friction,work reliable,high mechanical shock resistance.Vibration will be proceed under the condition of acceleration 0.7g. Due to the mobile part of ivot needle adopt spring bearing support which can reduce the shock and vibration, pivot needle and bearing consists of high hardness cobalt-tungsten and barklyite,vibration can be proceed under the condition of acceleration 0.7g.

Advanced converter line and Indicating device integration structure,the instrument is high accuracy and large angle.The meter have linear scale,and won't affect by the magnetic filed outside,all adopt printed dial,colorized dial,scale is very clear,look neat and beautiful.Null meter reading instrument all have zero button,easy to adjust.

Type:Alternating current (AC), Direct current(DC).

Product Description:

The deflection angle of Q96,F96,F96J,51L5,51T5,51C5,Z96,LS-96 Pointer needle is wide angle(240 to 250 degree) ,the meter is tension string structure,import of German technology,rotation no friction,shock assistance is better. Hairspring structure import of Taiwan technology,shock assistance is good,also can be produce to right angle 90 degree deflection angle.

The deflection angle of 51C4,51L4,51T4,51C6,51T6 Pointer needle is right angle(90 degree),also can be extend to wide angle(240 degree) deflection angle.(need to confirm when you place order) (96x96mm)

Q/F 96 type wide angle meter,overall size 96x96mm, hole size 92x92mm,depth dimensions 108mm.

Q/F 96 type right angle meter,overall size 96x96mm, hole size 92x92mm,depth dimensions 108mm.

Directions for use:

1.After the instrument is correctly connected, connect the power supply to the rated voltage, and the green indicator light will be on at this time, the instrument will be in the monitoring state, and the indicator value is the insulation resistance value of the power grid (excluding the self check file).

 

2.0.01MΩ、0.03MΩ、0.06MΩ、0.1MΩ、0.2M2, 0.5M2, 1.0M0 , 2M?. When the instrument is working, the alarm setting switch should be set at the position of the selected alarm value, which has 8 levels: 0.01M0,0.03M0,0.06M0, 0.1MQ,0.2MQ, 0.5MQ、 1.0MQ、 2MQ.

 

3.lf it is necessary to judge whether the instrument works normally, self inspection can be carried out.Set the switch at the back of the instrument to the self inspection gear, and the instrument will carry out self inspection. When the instrument can carry out normal self inspection, the pointer shall indicate the position of 0.01M2, and the alarm red light wil be on, and the alarm output terminal has output. After the self-test, the instrument must be restored to the normal alarm gear.

 

4.When connecting shore power,because the shore power system is a grounding system, the instrument will give false alarm, at this time, the switch can be adjusted to the "shore power" position; the instrument will indicate the position of 0.01M2, but the output normally open and normally closed contacts will not change action, and there is no alarm output.

 

Item Technical performance
Product technical standard: GB/T7676-1998
Service environment standard: GB8355-1987
Product safety standard: GB4793-2001
Accuracy grade Frequency 0.5 grade, Power factor meter 3.0 grade, other 1.5 grade
Service temperature -10~55℃,13℃~33℃conform to accuracy grade 100%
Rotation angle of needle Wide angle(250 degree) , Right angle(90 degree), Synchronous dial indicator
Protection grade Shell protection conform to IP42,allow the exist of oil mist,salt mist,dust etc.
Color of watchcase Square type white color, Round square black color ,panel border,terminal block,black.
Dial color Convention color white, black need to customized.
Direction of mounting Vertical
Front size of instrument Q/F96(96X96)mm,Q/F72(72X72)mm
New 45 type (110X110)mm,New 63 type (80X80)mm
Meter overshoot When the pointer needle reach 2/3 of ful scale,less than 20%
Insulation,Voltage-endurance electric circuit and shell AC:2600V / 1 minute(water area)
Vibration resistance 24.5m/S2
Shock resistance 147m/S2
Meter material square type: watchcase/terminal block(flame retardant ABS), Watch cap(transparent glass) Round square shape:water cap(transparent PC)



Send your message to us
ver_code